Radiation-resistant pressure transducers and signaling devices

Radiation-resistant pressure transducers PDA-RS, PID-RAS, PID-RAS are designed to measure the absolute, excess and differential pressure of controlled media with the formation of unified output signals.

 

Scope of application — systems for automatic control of parameters of nuclear power plants.

Upper limits of the measured absolute pressure
0,1; 1; 1,6; 2,5; 4; 6; 10; 16; 25; 40 MPa
Upper limits of the measured overpressure
0,1; 1; 1,6; 2,5; 4; 6; 10; 16; 25; 40 MPa
Upper limits of the measured differential pressure
- 6,3; 10; 16; 25; 40; 63 kPa
- - 0,1; 0,16; 0,25; 0,4; 0,63; 1,0; 1,6; 2,5 MPa at the maximum permissible operating overpressure of up to 25 MPa
The limit of the permissible basic reduced error of the converters
+/- 0,75%
Water vapor of the controlled environment
from 0 to +350 °C
Nitrogen of the controlled environment
from 0 to +350 °C
Controlled environment air
-40 to +100 °C
Controlled environment condensate
0 to +100 °C
Water of high purification of a controlled environment
from 0 to +350 °C
Ambient air temperature
from -2 to +55 °C
Relative humidity of the surrounding air
up to 100%
Absolute ambient air pressure
from 0.08 to 0.4 MPa with the presence of seawater and oil vapors
DC voltage Parameters
from 18 V to 34 V
AC voltage parameters
from 154 V to 231 V with a frequency of 50 Hz or 400 Hz
DC output signals from 4 to 20 mA
with a load resistance of up to 500 ohms
DC voltage output signals from 0 to 10 V
with a load resistance from 2 to 100 kohm
Digital output signal via the interface
RS-485
Relay output signal for signaling devices
according to the "dry contact"type

The delivery set of the pressure converter (alarm) of the group version includes:

 

  • primary measuring converter;
  • secondary converter group;
  • a permanent storage device module.

The housing of the secondary group converters can be supplied separately or together with the secondary group converters according to the order.

 

The housing of the secondary group converters is made in the form of a block in two versions:

 

  • to accommodate four secondary group converters;
  • to accommodate eight secondary group converters.

The design of the housing of the secondary group converter provides connection to each secondary group converter separately:

 

  • power supply circuits;
  • communication lines;
  • primary measuring converter;
  • a permanent storage device module.